TYPE TVE

Compact solution for low airflow velocities

Circular air terminal unit for use in variable air volume systems at low airflow velocities even under unfavourable upstream conditions


 


  • Effective tubeless pressure monitoring via damper blade
  • Effective pressure transmission through pressure channel in shaft
  • Terminals with protective cover – no junction boxes required
  • Any direction of flow with dynamic transducer
  • Suitable for airflow velocity of 0.5 – 13 m/s
  • Compact dimensions for use in confined ceiling areas
  • Plug-and-play solution in conjunction with X-AIRCONTROL room control
  • Exact measurement even at low airflow velocities
  • Any installation orientation even with static transducers
  • Closed blade air leakage tested to EN 1751, at least class 3
  • Casing air leakage tested to EN 1751, class C
  • Volume flow rate range 1:25

 


Optional equipment and accessories


  • Acoustic cladding for the reduction of case-radiated noise
  • Secondary silencer Type CA, CS or CF for the reduction of air-regenerated noise
  • Hot water heat exchanger Type WL and electric air heater Type EL for reheating the airflow

Application

Application
  • Circular VARYCONTROL VAV terminal unit for use in room air conditioning systems (HVAC systems)
  • Also for unfavourable upstream conditions at low airflow velocities for supply air or exhaust air flow control in variable air volume systems
  • Closed-loop volume flow control using an external power supply
  • For controlling, restricting, or shutting off the airflow in air conditioning systems
  • Shut-off by means of switching (equipment supplied by others)

Special characteristics
  • Highly effective pressure signal at a small angle of attack
  • Factory set-up or programming and aerodynamic function testing
  • Volume flow rate can be measured and subsequently adjusted on site; additional adjustment tool may be necessary (depending on the variant of the control component)
  • Effective tubeless pressure monitoring via damper blade
  • Effective pressure transmission through pressure channel in shaft
  • Suitable for any flow direction due to dynamic transducer
  • Any installation orientation even with static transducers
  • Suitable for airflow velocity of 0.5 – 13 m/s
  • Compact dimensions for use in confined ceiling areas

Nominal sizes

  • 100, 125, 160, 200, 250

DESCRIPTION

Variants
  • TVE: VAV terminal unit
  • TVE-D: VAV terminal unit with acoustic cladding
  • TVE-FL: VAV terminal unit with flanges on both ends
  • TVE-D-FL: VAV terminal unit with acoustic cladding and flanges on both ends
  • Unit with acoustic cladding and/or a secondary silencer Type CA, CS or CF for demanding acoustic requirements

Parts and characteristics
  • Ready-to-commission unit which consists of mechanical parts and control components.
  • Damper blade with integrated measuring unit
  • Shaft with effective pressure channel for measured value transmission
  • Factory assembled control components complete with wiring
  • Aerodynamic functional testing on a special test rig prior to shipping of each unit
  • Set-up data is given on a label or volume flow rate scale affixed to the unit
  • High control accuracy even in the case of unfavourable upstream conditions

Attachments
  • EASY controller: Compact unit consisting of controller with potentiometers, effective pressure transducer and actuator
  • Compact controller: Compact unit consisting of controller with potentiometers, effective pressure transducer and actuator
  • Compact controller Modbus: variant with Modbus RTU interface; Plug-and-play solution in conjunction with X-AIRCONTROL room control

Construction features

  • Circular casing
  • Spigot suitable for circular ducts to EN 1506 or EN 13180
  • Spigot with groove for double lip seal
  • Position of the damper blade indicated externally at position indicator
  • TVE-FL: Flanges to EN 12220
  • Control component can be replaced


Materials and surfaces

Galvanised sheet steel construction


  • Casing made of galvanised sheet steel
  • Control damper blade, effective pressure sensor and shaft made of plastic, PA6, UL94, flame retardant (V-0)
  • Damper blade seal made of plastic, TPU, microbacterial resistant
  • Plastic bearings

Powder-coated construction (P1)


  • Casing made of galvanised sheet steel, surface powder coated, silver grey (RAL 7001)
  • Control damper blade, effective pressure sensor and shaft made of plastic, PA6, UL94, flame retardant (V-0)
  • Damper blade seal made of plastic, TPU, microbacterial resistant
  • Plastic bearings

Stainless steel construction (A2)


  • Casing made of stainless steel 1.4301
  • Control damper blade, effective pressure sensor and shaft made of plastic, PA6, UL94, flame retardant (V-0)
  • Damper blade seal made of plastic, TPU, microbacterial resistant
  • Plastic bearings

Acoustic cladding


  • Variant with acoustic cladding (-D)
  • Acoustic cladding made of galvanised sheet steel
  • Rubber profile for the insulation of structure-borne noise
  • Lining is mineral wool

Mineral wool


  • Tested to EN 13501, fire rating class A1, non-combustible
  • RAL quality mark RAL-GZ 388
  • Biosoluble and hence hygienically safe according to the German TRGS 905 (Technical Rules for Hazardous Substances) and EU directive 97/69/EC

Standards and guidelines

  • Hygiene conforms to VDI 6022
  • Casing air leakage tested to EN 1751, class C

 


Closed blade air leakage:


NW 100 – 160


  • EN 1751, Class 3
  • Meets the general requirements of DIN 1946, part 4, with regard to the acceptable closed blade air leakage

 


NW 200 – 250


  • EN 1751, Class 4
  • Meets the increased requirements of DIN 1946, part 4, with regard to the acceptable closed blade air leakage

Nominal sizes

  • 100, 125, 160, 200, 250


Information technique

FUNCTION, TECHNICAL DATA, QUICK SIZING, SPECIFICATION TEXT, ORDER CODE

  • Function
  • TECHNICAL DATA
  • QUICK SIZING
  • SPECIFICATION TEXT
  • ORDER CODE
TVE_gc_02.ai.png

① Double lip seal
② Casing
③ Damper blade including effective pressure sensor
④ Shaft with effective pressure channel
⑤ Electronic volume flow controller


The control damper blade works as an actuator and as an effective pressure sensor. Through the effective pressure channel in the shaft of the detected effective pressure reaches the transducer (static or dynamic), is converted into an electrical signal and compared with the setpoint value.

In the case of a control deviation, the integrated actuator changes the position of the control damper blade. As a result, the volume flow rate is kept constant in close tolerances over the entire differential pressure range.

 


Nominal sizes100 – 250 mm
Volume flow rate range

4 – 637 l/s or 14 – 2293 m³/h

Volume flow rate control range (unit with dynamic effective pressure measurement)

Approx. 4 to 100 % of the nominal volume flow rate
Minimum differential pressure

<5 – 82 Pa

Maximum differential pressureControl component with dynamic transducer: 900 Pa, Control component with static transducer: 600 Pa
Operating temperature10 to 50 °C

Quick sizing tables provide a good overview of the room sound pressure levels that can be expected. Approximate intermediate values can be interpolated. Precise intermediate values and spectral data can be calculated with our Easy Product Finder design programme.
The first selection criteria for the nominal size are the actual volume flow rates qvmin and qvmax. The quick sizing tables are based on generally accepted attenuation levels. If the sound pressure level exceeds the required level, a larger air terminal unit and/or a silencer is required.



 

 


TVE, sound pressure level at differential pressure 150 Pa


NSqv [l/s]qv [m³/h]Air-regenerated noise [dB(A)]Case-radiated noise
1004142817<15<15<1515
10035127453126232817
10067241503429263322
10098354533631273625
12562126

<15

<15

<15

<15

<15

12558207453329252817
125109393504036333322
125161579534339363726
16010353728231917<15
16093333483834302821
160175631504036323124
160258929504036333326
200155527<15<15<15<15<15
2001505414635302726<15
2002851027483834313116
2004201513504036333520
2502487352518<1519<15
250228822474036343318
2504331558484239373823
2506372293494441394025

TVE, LPA
TVE, LPA1, with secondary silencer CS/CF, insulation thickness 50 mm, length 500 mm
TVE, LPA1, with secondary silencer CS/CF, insulation thickness 50 mm, length 1000 mm
TVE, LPA1, with secondary silencer CS/CF, insulation thickness 50 mm, length 1500 mm
TVE, LPA2
TVE-D, LPA3
The sound power levels for calculating the sound pressure levels were measured in the TROX laboratory according to DIN EN ISO 5135 - see "Basic information and nomenclature".


 











Circular VAV terminal units for variable and constant air volume systems, suitable for supply or extract air, available in five nominal sizes. High control accuracy even in case of unfavourable upstream conditions. Control range at least 1:25. Differential pressure detection and control via the control damper blade. Transmission of effective pressure tubeless through differential pressure channel in the shaft. Closed blade air leakage to EN 1751: at least class 3, from NS 200: class 4. Casing air leakage to EN 1751, class C. Ready-to-commission unit which consists of the mechanical parts and the factory installed electronic control component. Position of the damper blade can be seen from the outside on the control component. Damper blade is factory set to open position which allows ventilation airflow even without control.



Special characteristics

  • Highly effective pressure signal at a small angle of attack
  • Factory set-up or programming and aerodynamic function testing
  • Volume flow rate can be measured and subsequently adjusted on site; additional adjustment tool may be necessary (depending on the variant of the control component)
  • Effective tubeless pressure monitoring via damper blade
  • Effective pressure transmission through pressure channel in shaft
  • Suitable for any flow direction due to dynamic transducer
  • Any installation orientation even with static transducers
  • Suitable for airflow velocity of 0.5 – 13 m/s
  • Compact dimensions for use in confined ceiling areas


Materials and surfaces

Galvanised sheet steel construction


  • Casing made of galvanised sheet steel
  • Control damper blade, effective pressure sensor and shaft made of plastic, PA6, UL94, flame retardant (V-0)
  • Damper blade seal made of plastic, TPU, microbacterial resistant
  • Plastic bearings

Powder-coated construction (P1)


  • Casing made of galvanised sheet steel, surface powder coated, silver grey (RAL 7001)
  • Control damper blade, effective pressure sensor and shaft made of plastic, PA6, UL94, flame retardant (V-0)
  • Damper blade seal made of plastic, TPU, microbacterial resistant
  • Plastic bearings

Stainless steel construction (A2)


  • Casing made of stainless steel 1.4301
  • Control damper blade, effective pressure sensor and shaft made of plastic, PA6, UL94, flame retardant (V-0)
  • Damper blade seal made of plastic, TPU, microbacterial resistant
  • Plastic bearings

Acoustic cladding


  • Variant with acoustic cladding (-D)
  • Acoustic cladding made of galvanised sheet steel
  • Rubber profile for the insulation of structure-borne noise
  • Lining is mineral wool

Mineral wool


  • Tested to EN 13501, fire rating class A1, non-combustible
  • RAL quality mark RAL-GZ 388
  • Biosoluble and hence hygienically safe according to the German TRGS 905 (Technical Rules for Hazardous Substances) and EU directive 97/69/EC

Construction

  • Galvanised sheet steel
  • P1: Powder-coated, silver grey (RAL 7001)
  • A2: Stainless steel


Materialien und Oberflächen

Galvanised sheet steel construction


  • Casing made of galvanised sheet steel
  • Control damper blade, effective pressure sensor and shaft made of plastic, PA6, UL94, flame retardant (V-0)
  • Damper blade seal made of plastic, TPU, microbacterial resistant
  • Plastic bearings

Powder-coated construction (P1)


  • Casing made of galvanised sheet steel, surface powder coated, silver grey (RAL 7001)
  • Control damper blade, effective pressure sensor and shaft made of plastic, PA6, UL94, flame retardant (V-0)
  • Damper blade seal made of plastic, TPU, microbacterial resistant
  • Plastic bearings

Stainless steel construction (A2)


  • Casing made of stainless steel 1.4301
  • Control damper blade, effective pressure sensor and shaft made of plastic, PA6, UL94, flame retardant (V-0)
  • Damper blade seal made of plastic, TPU, microbacterial resistant
  • Plastic bearings

Acoustic cladding


  • Variant with acoustic cladding (-D)
  • Acoustic cladding made of galvanised sheet steel
  • Rubber profile for the insulation of structure-borne noise
  • Lining is mineral wool

Mineral wool


  • Tested to EN 13501, fire rating class A1, non-combustible
  • RAL quality mark RAL-GZ 388
  • Biosoluble and hence hygienically safe according to the German TRGS 905 (Technical Rules for Hazardous Substances) and EU directive 97/69/EC

Technichal Data

  • Minimum differential pressure: 5 – 82 Pa

Maximum differential pressure

  • Control component with dynamic transducer: 900 Pa
  • Control component with static transducer: 600 Pa


Auslegungsdaten
  • q _______________________ [m³/h]
  • Δpst _______________________ [Pa]

 Air-regenerated noise

  • LPA _______________________ [dB(A)]

 

Case-radiated noise

 


  • LPA _______________________ [dB(A)]
TVEDP1FL / 100 / D2 / XB0 / V0 / 200 – 900m³/h
||||||| ||||
1234567 891011
,
TVED / 200 / D2 / Easy
|||||
12567

1 Type


TVE Volume flow controller, circular


 


2 Acoustic cladding


No entry: none


D With acoustic cladding


 


3 Material (not Easy)


No entry: galvanised sheet steel


P1 Duct powder-coated, RAL 7001, silver grey


A2 Duct made of stainless steel


 


4 Duct interface (not Easy)


No entry: Insert with groove for double lip seal for duct to EN1506


FL Flanges on both ends


 


5 Nominal size [mm]


100, 125, 160, 200, 250


 


6 Accessories


No entry: none


D2 Double lip seal both sides (only with insertion with groove)


G2 Matching flange to each flange (only with FL)


 


7 Attachment (control component)


Easy Volume flow controller, dynamic, interface analog, setting qvmin and qvmax with potentiometers


XB0 Volume flow controller, dynamic, interface analogue


XM0 Volume flow controller, analogue interface and Modbus RTU, display


XM0-J6 Volume flow controller, analogue and Modbus RTU interface, display, RJ12 socket (for X-AIRCONTROL)


XS0 Volume flow controller, static, interface analogue and Modbus RTU, display


XS0-J6 Volume flow controller, static, interface analogue and Modbus RTU, display, RJ12 socket (for X-AIRCONTROL)


 


8 Operating mode (not Easy)


V Variable, setpoint value range (not for XM0-J6, XS0-J6)


F Constant value, a setpoint value (not for XM0-J6, XS0-J6)


M Modbus RTU interface (only selectable with XM0, XS0 attachment, mandatory for XM0-J6, XS0-J6)


 


9 Signal voltage range (not with Easy, operating mode M)


0 0 – 10V DC


2 2 – 10V DC


 


10 Operating values ​​for factory setting (not for Easy)


Volume flow rates in [m³/h or l/s] see unit


qvconst (in operating mode F)


qvmin-qvmax (in operating mode V, M)


 


11 Unit (not Easy)


m³/h Volume flow rates in m³/h


l/s Volume flow rates in l/s

,

1 Type


TVE VAV terminal unit


 


2 Acoustic cladding


No entry: none


D With acoustic cladding


 


5 Nominal size [mm]


100, 125, 160, 200, 250


 


6 Accessories


No entry: none


D2 Double lip seal both sides


 


7 Attachments (control components)


Easy Easy controller


Order example: TVE/200/D2/XB0/V0/500–1200 m³/h


Acoustic cladding Without
Material Galvanised sheet steel
Flange Without
Nominal size 200 mm
Accessories Double lip seal both sides
Attachment Compact controller
Operating mode Variable
Signal voltage range 0 – 10V DC
Volume flow rate

500 – 1200 m³/h

,

Order example: TVE-D/125/D2/Easy

Acoustic claddingWith
MaterialGalvanised sheet steel
Nominal size200 mm
AccessoriesDouble lip seal both sides
AttachmentEasy controller

Variants, Product details, Further Productinformations

  • VARIANTS
  • DIMENSIONS
  • PRODUCT DETAILS
  • FURTHER PRODUCTINFORMATIONS

 

  • VAV terminal unit for variable volume flow control
  • Spigot
  • Air terminal unit with acoustic cladding for variable volume flow control
  • For rooms where the case-radiated noise of the unit is not sufficiently reduced by a false ceiling
  • The circular ducts for the room under consideration must have adequate acoustic insulation (provided by others) on the fan and room ends
  • Acoustic cladding cannot be retrofitted

,

 

  • VAV terminal unit for variable volume flow control
  • With flanges on both ends to make detachable connections to the ducting
  • Optional available with matching flanges

,
  • Air terminal unit with acoustic cladding for variable volume flow control
  • With flanges on both ends to make detachable connections to the ducting
  • Optional available with matching flanges
  • For rooms where the case-radiated noise of the unit is not sufficiently reduced by a false ceiling
  • The circular ducts for the room under consideration must have adequate acoustic insulation (provided by others) on the fan and room ends
  • Acoustic cladding cannot be retrofitted

NSLA∅Dkg
100310135993,3
1253101481243,6
1604001651594,2
2004001851995,1
2504002102496,1
,
NSLL₁A∅D∅D₃kg
100310232135991987,2
1253102321481242238,5
16040031216515925811
20040031218519929812,9
25040031221024934815,9
,
NSLA∅D∅D₁∅D₂nDkg
10029013599132152443,9
125290148124157177444,2
160380165159192212645,3
200380185199233253646,5
250380210249283303647,8
,
NSLL₁A∅D∅D₁∅D₂∅D₃nDkg
10029023213599132152198447,8
125290232148124157177223449,1
1603803121651591922122586412,1
2003803121851992332532986414,3
2503803122102492833033486417,6
Installation and commissioning
  • Any installation orientation
  • TVE-D: For constructions with acoustic cladding, ducts on the room side should have cladding up to the acoustic cladding of the controller

Upstream conditions


The effective pressure, which is decisive for the volume flow rate, is recorded and averaged on the control damper blade. Therefore, the volume flow rate accuracy Δqv is independent of the upstream section.


Duct connections, e.g. branches off the main duct, must comply with EN 1506 and EN 13180.


 

TVE control components VARYCONTROL

 

AttachmentControlled variableCategory, Interface, CharacteristicsDifferential pressure transmitterActuator
EasyqvEasy controllerDynamic

integrated
integrated
XB0qvCompact controllerDynamic

integrated
integrated
XM0qvCompact controller

Analogue and Modbus RTU

Display
Dynamic

integrated
integrated
XM0–J6qvCompact controller

Analogue and Modbus RTU with RJ12 socket

Display
Dynamic

integrated
integrated
XS0qvCompact controller

Analogue and Modbus RTU

Display
Static

integrated
integrated
XS0–J6qvCompact controller

Analogue and Modbus RTU with RJ12 socket

Display
Static

integrated
integrated

qv Volume flow rate


Téléchargements

Information produit

Certificats

Manuels d'utilisation

Partager la page

Recommander cette page

Vous avez la possibilité de recommander cette page en partageant le lien.

Les champs marqués d'une étoile (*) sont obligatoires.

Contact

Merci pour votre message !

Votre recommandation a été envoyée et sera bientôt reçue par le destinataire.

Contact

Nous sommes à votre disposition

Visual contact Visual contact

Veuillez préciser votre message et le type de demande.
Tel.: +41 26 425 59 00 | Fax: +41 26 425 59 01

Les champs marqués d'une étoile (*) sont obligatoires.

Contact

Merci pour votre message !

Visual contact Visual contact

Votre message a été envoyé et sera traité dans les plus brefs délais.
Notre département de traitement des demandes prendra contact avec vous dès que possible.
Pour les questions d'ordre général concernant les produits ou services, vous pouvez aussi nous appeler :
Tel.: +41 26 425 59 00 | Fax: +41 26 425 59 01

Contact

Nous sommes à votre disposition

Visual contact Visual contact

Veuillez préciser votre message et le type de demande.
Tel.: +41 26 425 59 00 | Fax: +41 26 425 59 01

Pièce jointe (max. 10MB)

Les champs marqués d'une étoile (*) sont obligatoires.

Contact

Merci pour votre message !

Visual contact Visual contact

Votre message a été envoyé et sera traité dans les plus brefs délais.
Notre département de traitement des demandes prendra contact avec vous dès que possible.
Pour les questions d'ordre général concernant les produits ou services, vous pouvez aussi nous appeler :
Tel.: +41 26 425 59 00 | Fax: +41 26 425 59 01