1 Differential pressure sensor
2 Double lip seal
3 Inspection access
4 Damper blade
5 Integrated silencer
6 Control components, e.g. Easy controller
Nominal sizes | 125 – 400 mm |
Volume flow range | 14 - 2007 l/s or 50 - 7228 m³/h |
Volume flow control range (unit with dynamic differential pressure measurement) | Approx. 10 - 100 % of the nominal volume flow |
Minimum differential pressure | Up to 123 Pa (without secondary silencer) |
Maximum differential pressure | 1000 Pa |
Operating temperature | 10 to 50 °C |
Air-regenerated noise
| TVZ | – | D | / | 160 | / | D1 | / | Easy |
| | | | | | | | | | | ||||
| 1 | 2 | 3 | 4 | 5 | ||||
TVZ VAV terminal unit, supply air
2 Acoustic cladding
No entry: none
D With acoustic cladding
3 Nominal size [mm]
125, 160, 200, 250, 315, 400
4 Accessories
No entry: none
D1 Double lip seal
5 Attachments (control component)
Easy Volume flow controller, dynamic, analogue interface, setting of qvmin and qvmax with potentiometers (provided on site)
| Acoustic cladding | With |
| Nominal size | 200 mm |
| Attachments (control components) | Easy volume flow controller, dynamic, analogue interface, setting of qvmin and qvmax with potentiometers |
| TVZ | – | D | / | 160 | / | D1 | / | XB4 | / | V | 0 | / | 200 – 900 [m³/h] | / | NO |
| | | | | | | | | | | | | | | | | | | |||||||
| 1 | 2 | 3 | 4 | 5 | 7 | 8 | 9 | 10 | |||||||
2 Acoustic cladding
No entry: none
D With acoustic cladding
3 Nominal size [mm]
125, 160, 200, 250, 315, 400
4 Accessories
No entry: none
D1 Double lip seal
5 Attachments (control component)
For example
BC0 Compact controller
XB4 Universal controller (VARYCONTROL)
7 Operating mode
F Constant value mode, one setpoint value (no external switch contact)
V Variable operation (adjustable setpoint value range)
8 Signal voltage range
For the actual and setpoint value signals
0 0 – 10 V DC
2 2 – 10 V DC
9 Operating values for factory setting
Volume flow rate [m³/h or l/s]
qᵥconst (with operating mode F)
qᵥmin – qᵥmax (with operating mode V)
10 Damper blade position
Only with spring return actuators
NO power off to open (Normally Open)
NC power off to close (Normally Closed)
| Acoustic cladding | with |
| Nominal size | 160 mm |
| Accessories | Double lip seal |
| Attachments (control component) | Compact controller, dynamic, analogue interface |
| Operating mode | Variable |
| Signal voltage range | 0 – 10 V DC |
| Operating values | qᵥmin = 180 m³/h qᵥmax = 850 m³/h |
Share page
Recommend this page
Recommend this page by sending a link by mail.
Share page
Thank you for your recommendation!
Your recommendation has been sent and should arrive shortly.
Contact
We are here for you
Please specify your message and type of request
Tel.: +41 55 250 71 11 | Fax: +41 55 250 73 10
Contact
Thank you for your message!
Your message is send and will be processed shortly.
Our department for Service-Requests will contact you asap.
For general question regarding products or services you can also call:
Tel.: +41 55 250 71 11 | Fax: +41 55 250 73 10
Contact
We are here for you
Please specify your message and type of request
Tel.: +41 55 250 71 11 | Fax: +41 55 250 73 10
Contact
Thank you for your message!
Your message is send and will be processed shortly.
Our department for Service-Requests will contact you asap.
For general question regarding products or services you can also call:
Tel.: +41 55 250 71 11 | Fax: +41 55 250 73 10